Product Overview
The ZW32Y-12 outdoor AC high voltage prepaid vacuum circuit breaker is designed for prepaid high-voltage metering applications in three-phase AC 50 Hz power systems with a rated voltage of 12 kV. Comprising a ZW32-12 outdoor vacuum circuit breaker, voltage transformer, current transformer, and intelligent metering controller, it integrates the functions of a high-voltage switchgear and a high-voltage metering device. It provides capabilities such as load control, high-voltage metering, prepaid function, overload current protection, inrush current delay protection, short-circuit instantaneous protection, and anti-tampering protection. By incorporating a GPRS network load control terminal, it enables real-time and scheduled meter reading, remote power disconnection/connection, and line loss analysis.
The ZW32Y-12 outdoor high voltage prepaid vacuum circuit breaker complies with national standards such as GB1984-2003, GB/17215-2002, and GB17201-2007.
Technical Specifications
|
S.Q. |
Name |
Unit |
Data |
||
|
1 |
Rated Voltage |
kV |
12 |
||
|
2 |
Rated Frequency |
Hz |
50 |
||
|
3 |
Rated Current |
A |
630/1250 |
||
|
4 |
Rated Short-Circuit Breaking Current |
kA |
16 |
20 |
|
|
5 |
Rated Short-Time Withstand Current |
16 |
20 |
||
|
6 |
Rated Peak Withstand Current (Peak) |
40 |
50 |
||
|
7 |
Rated Short-Time Duration |
S |
4 |
||
|
8 |
Rated Short-Circuit Making Current (Peak) |
50 |
|||
|
9 |
1 min Power Frequency Withstand Voltage |
Phase-to-Phase, |
kV |
42 |
|
|
10 |
Across Isolating Gap |
48 |
|||
|
11 |
Lightning Impulse Withstand Voltage |
Phase-to-Phase, |
75 |
||
|
12 |
Across Isolating Gap |
85 |
|||
|
13 |
Rated Operating Sequence |
times |
O-0.3S-CO-180SCO |
||
|
14 |
Rated Number of Current Breaking Operations |
10000 |
|||
|
15 |
Rated Number of Short-Circuit Breaking Operations |
50 |
|||
|
16 |
Mechanical Life |
10000 |
|||
|
17 |
Power Frequency Withstand Voltage for Secondary Circuits (1 min, excluding electronic components) |
V |
2000 |
||
Model and Designation
Z W 32Y -12 / □ - □
Z: Vacuum Circuit Breaker
W: Outdoor Type
32Y: Design Symbol (Prepaid)
12: Rated Voltage (kV)
□: Rated Current (A)
□: Rated Short-Circuit Breaking Current (kA)
Normal Service Conditions
1. Altitude: Not exceeding 2000 meters.
2. Ambient Air Temperature: -45℃ to +40℃.
3. Relative Humidity: Daily average not exceeding 95%; Monthly average not exceeding 90%.
4. Wind Speed: Not exceeding 35 m/s.
5. Installation Site: Free from fire, explosion hazards, chemical corrosion, and severe vibration.
6. Pollution Degree: Class III.
Hot Tags: zw32y-12 series outdoor ac high voltage prepaid vacuum circuit breaker, China zw32y-12 series outdoor ac high voltage prepaid vacuum circuit breaker manufacturers, suppliers, factory, outdoor vacuum circuit breaker, ZW30A 40 5 Series Outdoor High Voltage Vacuum Circuit Breaker, ZW32Y 12 Series Outdoor AC High Voltage Prepaid Vacuum Circuit Breaker, ZW32 12 Series Outdoor AC High Voltage Vacuum Circuit Breaker, ZW39 40 5 Series Outdoor High Voltage Vacuum Circuit Breaker, ZW17 40 5 Series Outdoor High Voltage Vacuum Circuit Breaker