Core Positioning
This product series represents a versatile and cost-effective three-phase distribution transformer designed for end-users in 10kV and below distribution networks. Widely used in industrial, commercial, residential areas, infrastructure, and distributed generation integration scenarios, it serves as a primary component for the safe and reliable conversion from medium-voltage distribution to low-voltage (400V) power consumption.
Technical Specifications
|
Rated capacity |
Rated voltage and tapping range |
Vector group |
No Load Current |
Short-circuit impedance |
No load Losses |
On load Losses(W)(11) |
|||
|
HV |
Tapping range |
LV |
Dyn11/Yzn11 |
Yyn0 |
|||||
|
30 |
10 |
±2×2.5 ±5 |
0.4 |
Dyn11 |
1.2 |
4 |
65 |
455 |
430 |
|
50 |
1.04 |
80 |
655 |
625 |
|||||
|
63 |
0.96 |
90 |
785 |
745 |
|||||
|
80 |
0.96 |
105 |
945 |
900 |
|||||
|
100 |
0.88 |
120 |
1140 |
1080 |
|||||
|
125 |
0.88 |
135 |
1360 |
1295 |
|||||
|
160 |
0.8 |
160 |
1665 |
1585 |
|||||
|
200 |
0.8 |
190 |
1970 |
1870 |
|||||
|
250 |
0.72 |
230 |
2300 |
2195 |
|||||
|
315 |
0.72 |
270 |
2760 |
2630 |
|||||
|
400 |
0.64 |
330 |
3250 |
3095 |
|||||
|
500 |
0.64 |
385 |
3900 |
3710 |
|||||
|
630 |
0.48 |
4.5 |
460 |
4460 |
|||||
|
800 |
0.48 |
560 |
5400 |
||||||
|
1000 |
0.48 |
665 |
7415 |
||||||
|
1250 |
0.4 |
780 |
8640 |
||||||
|
1600 |
0.4 |
940 |
10440 |
||||||
|
2000 |
0.32 |
5 |
1085 |
13180 |
|||||
|
2500 |
0.32 |
1280 |
15270 |
||||||
Core Advantages and Features
1. Comprehensive Voltage Compatibility and Flexible Tapping Configuration:
- The high-voltage side is fully compatible with common domestic and international distribution voltage standards, including 6kV, 6.3kV, 10kV, and 10.5kV. It offers two off-circuit tap-changing options, ±2×2.5% or ±5%, to meet the requirements of different grid environments.
- The low-voltage side provides a standard output of 0.4kV, directly supplying power to end-use equipment.
2. Diverse Vector Group Selection:
- Offers three standard vector groups: Dyn11, Yzn11, and Yyn0. Users can flexibly select based on specific requirements of the power supply system regarding harmonic suppression, unbalanced load capability, grounding methods, and relay protection, ensuring high adaptability.
3. Excellent Energy Savings and Economy:
- The capacity range spans from 30 kVA to 2500 kVA, meeting the full spectrum of needs from small commercial sites to medium-scale industrial loads.
- Designed with low losses, the no-load current is as low as 0.32%. Both no-load and load losses (corresponding to different vector groups) are optimized to comply with energy efficiency standards, resulting in low lifecycle operating costs.
4. High Reliability and Easy Maintenance:
- Short-circuit impedance is reasonably designed (4%, 4.5%, 5%), effectively limiting low-voltage side short-circuit currents.
- The off-circuit tap-changing structure is simple and reliable. The oil-immersed insulation provides good heat dissipation, making it suitable for various installation environments, both outdoor and indoor, with low maintenance requirements.
Typical Applications
10kV distribution substations, pole-mounted transformers, and pad-mounted substations in urban and rural power grids.
Distribution rooms for various buildings such as factories, shopping malls, schools, hospitals, and residential communities.
10kV grid-connection step-up transformers for distributed generation sources like photovoltaic and wind power.
Auxiliary power supply systems for infrastructure such as railways, highways, and airports.
Hot Tags: 10kv oil-immersed nltc distribution transformer, China 10kv oil-immersed nltc distribution transformer manufacturers, suppliers, factory, 10kV Oil Immersed NLTC Transformer for New Energy Applications, 10kV Oil Immersed NLTC Distribution Transformer, 10kV Oil Immersed OLTC Power Transformer, 10kv oil immersed transformer, 500kv transformer