330kV Oil-Immersed Three-Phase Two-Winding Power Transformer
video
330kV Oil-Immersed Three-Phase Two-Winding Power Transformer

330kV Oil-Immersed Three-Phase Two-Winding Power Transformer

Our 330kV oil-immersed three-phase two-winding off-circuit tap-changing power transformers are designed for 330kV transmission networks and large-scale power systems.

• Rated from 90 MVA to 720 MVA with HV options at 345kV and 363kV.

• ±2×2.5% off-circuit tapping range; LV options from 10.5kV to 20kV.

• No-load current as low as 0.16% with optimized losses reduces lifecycle operating costs.

• YNd11 vector group with 14%–15% short-circuit impedance ensures reliable protection and system stability.

• Oil-immersed construction for main substations, power plants, and renewable energy step-up applications. ```

 

Core Positioning

 

This product series is a standardized main transformer developed for 330kV extra-high voltage power grids and large-scale power systems. As the core equipment for power transmission and voltage conversion in regional networks, it has become the most widely adopted main transformer choice in substation configurations due to its cost-effectiveness and broad applicability.

 

Technical Parameters

 

(MVA)
Rated Capacity

Rated Voltage and Tapping Range

Vector Group

No Load Current
(%)

Short-circuit Impedance
(%)

No load Losses
(kW)

On load Losses
(kW)

HV
(kv)

Tapping Range

LV
(kv)

90000

345
363

±2×2.5

10.5
13.8
15.75
18
20

YNd11

0.35

14~15

37

247

120000

0.35

47

306

150000

0.33

56

362

180000

0.3

64

415

240000

0.27

80

515

360000

0.27

109

722

370000

0.24

111

736

400000

0.24

118

780

720000

0.16

183

1212

 

Advantages

 

1. Broad Capacity Coverage and Application Flexibility

The series covers a complete capacity range from 90 MVA to 720 MVA, providing suitable solutions for applications from regional load centers to large-scale power source grid integration. The HV side accommodates both 345kV and 363kV system voltages with ±2×2.5% off-circuit tapping capability to meet operational requirements across different regional networks.

2. Refined Electrical Performance

Five standard LV voltage options are available from 10.5kV to 20kV, matching the requirements of power plant auxiliary systems, industrial distribution networks, and urban power grids. The no-load current ranges from 0.16% to 0.35%, reflecting advanced core material and assembly techniques. Load losses are precisely controlled across all capacities. This low-loss design translates directly into reduced lifecycle operating costs.

3. Proven Reliability

The YNd11 vector group is a well-established connection scheme ensuring broad system compatibility and simplified protection coordination. Short-circuit impedance is maintained in the 14% to 15% range, effectively limiting fault currents while maintaining proper voltage regulation. The oil-immersed construction provides reliable insulation and cooling performance for long-term operation.

 

Applications:

 

- Main transformers for 330kV regional substations and terminal substations

- Generator step-up units or HV auxiliary transformers for thermal, hydro, and nuclear power plants

- Main step-up transformers for wind and solar PV farm collection substations

- Primary transformation equipment for large industrial and mining facility substations

Hot Tags: 330kv oil-immersed three-phase two-winding power transformer, China 330kv oil-immersed three-phase two-winding power transformer manufacturers, suppliers, factory, 330kV Oil Immersed Three Phase Two Winding Power Transformer, 330kV Oil Immersed Three Phase Three Winding Power Transformer, 330kv power transformer