This series is a cost-effective, reliable, and structurally straightforward standard two-winding main power transformer designed for 220kV high-voltage grids. With its mature, proven design and excellent operational economy, it is widely used in regional substations, end-user applications, and renewable energy power plants, serving as a core and fundamental component for power transmission between high-voltage grids and medium-voltage distribution networks.
Technical Specifications
|
(MVA) |
Rated Voltage and Tapping Range |
Vector Group |
No Load Current |
Short-circuit Impedance |
No load Losses |
On load Losses |
||
|
HV |
Tapping Range |
LV |
||||||
|
31500 |
220 |
±2×2.5 |
6.3 |
YNd11 |
0.45 |
12~14 |
15 |
115 |
|
40000 |
0.45 |
18 |
134 |
|||||
|
50000 |
0.42 |
21 |
161 |
|||||
|
63000 |
0.42 |
25 |
188 |
|||||
|
75000 |
10.5 |
0.38 |
29 |
213 |
||||
|
90000 |
0.35 |
34 |
246 |
|||||
|
120000 |
0.35 |
41 |
304 |
|||||
|
150000 |
10.5 |
0.32 |
49 |
360 |
||||
|
160000 |
0.31 |
51 |
378 |
|||||
|
180000 |
0.29 |
56 |
413 |
|||||
|
240000 |
0.26 |
70 |
484 |
|||||
Core Advantages and Features
1. Mature, Reliable, and Economical:
- Features a classic two-winding, oil-immersed, off-circuit tap-changing design. The structure is mature and proven, with simple operation and maintenance, offering significant advantages in total lifecycle cost.
- The high-voltage side supports standard voltages of 220kV and 242kV, equipped with a ±2×2.5% off-circuit tap-changer to accommodate normal system voltage fluctuations.
2. Flexible Capacity and Voltage Matching:
- Offers a wide range of standard capacities from 31.5 MVA to 240 MVA, meeting the requirements of power transmission and transformation projects of various scales.
- The low-voltage side primarily provides common industrial and distribution voltage levels such as 6.3kV, 6.6kV, 10.5kV, and 13.8kV, precisely matching end-user connection needs.
3. Optimized Electrical Performance:
- Employs the standard YNd11 vector group, ensuring good system compatibility and straightforward protection configuration.
- Short-circuit impedance is designed between 12% and 14%, achieving an optimal balance between limiting short-circuit currents and maintaining voltage stability.
- The no-load current is as low as 0.26%. Both no-load and load losses are systematically optimized, ensuring high operational energy efficiency.
Typical Applications
- Main transformers for 220kV regional substations and end-user substations.
- Main transformers for step-up substations in renewable energy projects such as wind farms and photovoltaic power plants.
- Main step-down transformers for large-scale industrial enterprises.
- Key nodes in urban power grids responsible for power transmission and distribution.
Hot Tags: 220kv oil-immersed 3-phase 2-winding nltc power transformer, China 220kv oil-immersed 3-phase 2-winding nltc power transformer manufacturers, suppliers, factory, 220kV Oil Immersed 3 Phase 2 Winding NLTC Power Transformer, 220kV Oil Immersed 3 Phase 2 Winding OLTC Power Transformer, 220kV Oil Immersed 3 Phase 3 Winding OLTC Power Transformer, 220kv power transformer