Product Overview
This series is an intelligent voltage-regulating two-winding main power transformer designed for 110kV grid users requiring strict voltage stability and power quality.
By integrating proven transformer technology with online on-load tap-changing (OLTC) functionality, it provides an ideal solution for dynamic voltage optimization, ensuring a continuous and high-quality power supply to critical loads.

Technical Specifications
|
Rated capacity |
Rated voltage and tapping range |
Vector group |
No Load Current |
Short-circuit impedance |
No load Losses |
On load Losses |
||
|
HV |
Tapping range |
LV |
||||||
|
6300 |
110 |
±4×1.25 |
6.3 |
YNd11 |
0.51 |
10.5 |
4.4 |
32 |
|
8000 |
0.51 |
5.3 |
38 |
|||||
|
10000 |
0.47 |
6.2 |
45 |
|||||
|
12500 |
0.47 |
7.4 |
53 |
|||||
|
16000 |
0.44 |
8.9 |
66 |
|||||
|
20000 |
0.44 |
10.6 |
79 |
|||||
|
25000 |
0.41 |
12.5 |
94 |
|||||
|
31500 |
0.41 |
14.9 |
111 |
|||||
|
40000 |
0.37 |
10.5~18 |
17.8 |
140 |
||||
|
50000 |
0.37 |
21 |
175 |
|||||
|
63000 |
0.34 |
25 |
209 |
|||||

Core Advantages
- Dynamic Voltage Regulation (OLTC): Standard equipped with ±4×1.25%, ±6×1.25%, or ±8×1.25% tap ranges. Enables real-time voltage adjustment without power interruption. Prevents production downtime caused by grid fluctuations.
- Flexible System Integration: HV rated at 110kV. LV side provides multiple distribution and industrial voltages (6.3kV, 6.6kV, 10.5kV, 21kV), perfectly matching various end-user connection scenarios.
- Optimized Reliability & Efficiency: Standard YNd11 vector group simplifies relay protection. Short-circuit impedance is optimized for system stability, while no-load current is kept low (min 0.34%) to balance regulation precision with energy savings.
- Wide Capacity Coverage: Ranging from 6.3 MVA to 63 MVA. Suitable for small-to-medium regional substations, industrial step-down substations, renewable energy grid connections, and user substations with strict power quality requirements.

Typical Applications
- 110kV substations in urban areas and industrial parks with strict requirements for voltage qualification rates.
- Dedicated substations for critical power users such as data centers, high-end manufacturing, and public infrastructure.
- Step-up substations for renewable energy projects (wind/PV), especially suitable for grid connection points with significant voltage fluctuations.
- Regional grid interconnection substations serving voltage support and regulation functions.
Hot Tags: 110kv oil-immersed 3-phase 2-winding oltc power transformer, China 110kv oil-immersed 3-phase 2-winding oltc power transformer manufacturers, suppliers, factory, 110kv power transformer, 110kV Oil Immersed 3 Phase 3 Winding OLTC Power Transformer, power transformer, 110kV Oil Immersed 3 Phase 2 Winding OLTC Power Transformer, pad mounted transformer, 110kV Oil Immersed 3 Phase 2 Winding NLTC Power Transformer