Core Positioning:
This product series represents a high-precision, intelligent voltage-regulating three-winding transformer designed for critical 110kV grid hubs with stringent requirements for voltage stability and power supply quality. It deeply integrates multi-voltage level capability with online on-load tap-changing (OLTC) technology, making it the preferred high-end solution for ensuring continuous, high-quality power supply to important loads and enabling dynamic grid voltage optimization management.
Technical Specifications:
|
Rated capacity |
Rated voltage and tapping range |
Vector group |
No Load Current |
Short-circuit impedance |
No load Losses |
On load Losses |
||
|
HV |
Tapping range |
LV |
||||||
|
6300 |
110 |
±4×1.25 |
6.3 |
YNyn0d11 |
0.61 |
HV~MV: |
5.3 |
40 |
|
8000 |
61 |
6.3 |
48 |
|||||
|
10000 |
0.57 |
7.5 |
56 |
|||||
|
12500 |
0.57 |
8.9 |
67 |
|||||
|
16000 |
0.54 |
10.6 |
81 |
|||||
|
20000 |
0.54 |
12.5 |
95 |
|||||
|
25000 |
0.5 |
14.9 |
113 |
|||||
|
31500 |
5 |
17.7 |
134 |
|||||
|
40000 |
0.46 |
21.2 |
161 |
|||||
|
50000 |
0.46 |
25 |
192 |
|||||
|
63000 |
0.42 |
29.8 |
230 |
|||||
Core Advantages and Features:
1. Real-time Dynamic Voltage Precision Control:
- Integrated On-Load Tap-Changer (OLTC) provides three fine-tuning ranges: ±4×1.25%, ±6×1.25%, and ±8×1.25%. It enables continuous online adjustment of the high-voltage side voltage without power interruption, ensuring highly stable output voltage on the medium and low-voltage sides despite grid fluctuations or rapid load changes, significantly enhancing power supply reliability and power quality.
2. Compact Integration and Multi-interface Compatibility:
- Utilizes an integrated three-winding (High Voltage, Medium Voltage, Low Voltage) design. A single unit can meet the interconnection and power distribution requirements between high-voltage transmission grids (110kV), medium-voltage distribution networks (e.g., 35kV, implied by impedance), and low-voltage user sides (6.3-11kV), greatly optimizing substation spatial layout and system architecture.
- The standard low-voltage side offers multiple common distribution voltages, including 6.3kV, 6.6kV, 10.5kV, and 11kV, adapting to various industrial and commercial user needs.
3. Optimized Impedance Design and System Compatibility:
- Employs a fixed short-circuit impedance configuration (HV-MV: 10.5%, HV-LV: 17.5~19%, MV-LV: 6.5%), facilitating coordinated system short-circuit current control and protection coordination, thereby enhancing grid operational stability.
- Utilizes the standard YNyn0d11 vector group, a mature and widely compatible technology for easy integration with existing grids.
4. Balanced High Performance and Economy:
- The capacity range spans from 6.3 MVA to 63 MVA, comprehensively meeting the needs of regional hub substations, important user substations, and renewable energy grid-connection points.
- While providing dynamic voltage regulation, advanced electromagnetic design and manufacturing processes keep the no-load current at a relatively low level (minimum 0.42%), achieving an excellent balance between functionality and energy efficiency.
Typical Applications:
- 110kV urban core area substations with critical requirements for voltage qualification rates.
- Dedicated substations for important power users such as large data centers, high-end manufacturing facilities, and research institutions.
- Regional grid interconnection substations or renewable energy collection stations serving voltage support and regulation functions.
- Comprehensive hub substations requiring multi-voltage level integration and automatic voltage regulation capability.
Hot Tags: 110kv oil-immersed 3-phase 3-winding oltc power transformer, China 110kv oil-immersed 3-phase 3-winding oltc power transformer manufacturers, suppliers, factory, 110kv power transformer, 110kV Oil Immersed 3 Phase 3 Winding OLTC Power Transformer, power transformer, 110kV Oil Immersed 3 Phase 2 Winding OLTC Power Transformer, pad mounted transformer, 110kV Oil Immersed 3 Phase 2 Winding NLTC Power Transformer