Product Overview
The 126kV Dry-Type Capacitive Transformer Composite Bushing (Through Rod Type) is a key insulation and current-carrying component specifically designed for high-voltage electrical equipment at the 126kV level. It features a fully sealed dry-type capacitive core and a high-performance silicone rubber composite housing, making it suitable for conductor wall- or tank-penetration insulation in transformers, reactors, GIS, and similar equipment. The product offers excellent electrical performance, mechanical strength, and environmental adaptability.
This series provides five current ratings from 630A to 2500A, meeting the insulation and current-carrying requirements of equipment with varying capacities. Suitable for installations at altitudes up to 1000 meters above sea level, it serves as a safe, reliable, and maintenance-free core insulation component in high-voltage transmission and distribution systems.
Technical Specifications
| Model | FBRG-126/630 | FBRG-126/1250 | FBRG-126/1600 | FBRG-126/2000 | FBRG-126/2500 |
| Rated Voltage (Ur) | 126 kV | 126 kV | 126 kV | 126 kV | 126 kV |
| Rated Current (Ir) | 630 A | 1250 A | 1600 A | 2000 A | 2500 A |
| Creepage Distance | 3900 mm | 3960 mm | 3906 mm | 3900 mm | 3906 mm |
| Altitude | 1000 m | 1000 m | 1000 m | 1000 m | 1000 m |
| Dielectric Dissipation Factor (tan δ) | >0.5% | >0.5% | >0.5% | >0.5% | >0.5% |
| External Insulation Material | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber |
| Partial Discharge (at 1.5Um/√3) | ≤10 pC | ≤10 pC | ≤10 pC | ≤10 pC | ≤10 pC |
| Color | Grey | Grey | Grey | Grey | Grey |
| Power Frequency Withstand Voltage | 255 kV | 255 kV | 255 kV | 255 kV | 255 kV |
| Standard Compliance | IEC 60137 | IEC 60137 | IEC 60137 | IEC 60137 | IEC 60137 |
| Lightning Impulse Withstand Voltage | 550 kV | 550 kV | 550 kV | 550 kV | 550 kV |
| Terminal Material | Tin-plated copper | Tin-plated copper | Tin-plated copper | Tin-plated copper | Tin-plated copper |
| Model | FBRGL-126/630 | FBRGL-126/1250 | FBRGL-126/1600 | FBRGL-126/2000 | FBRGL-126/2500 |
| Rated Voltage (Ur) | 126 kV | 126 kV | 126 kV | 126 kV | 126 kV |
| Rated Current (Ir) | 630 A | 1250 A | 1600 A | 2000 A | 2500 A |
| Creepage Distance | 3906 mm | 396 mm | 396 mm | 396 mm | 3906 mm |
| Altitude | 1000 m | 1000 m | 1000 m | 1000 m | 1000 m |
| Dielectric Dissipation Factor (tan δ) | >0.5% | >0.5% | >0.5% | >0.5% | >0.5% |
| External Insulation Material | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber | Silicone rubber |
| Partial Discharge (at 1.5Um/√3) | ≤10 pC | ≤10 pC | ≤10 pC | ≤10 pC | ≤10 pC |
| Color | Grey | Grey | Grey | Grey | Grey |
| Power Frequency Withstand Voltage | 255 kV | 255 kV | 255 kV | 255 kV | 255 kV |
| Standard Compliance | IEC 60137 | IEC 60137 | IEC 60137 | IEC 60137 | IEC 60137 |
| Lightning Impulse Withstand Voltage | 550 kV | 550 kV | 550 kV | 550 kV | 550 kV |
| Terminal Material | Tin-plated copper | Tin-plated copper | Tin-plated copper | Tin-plated copper | Tin-plated copper |
Hot Tags: 126kv composite housed rod type bushing, China 126kv composite housed rod type bushing manufacturers, suppliers, factory, 126kV Porcelain Housed Rod Type Bushing, 126kV Composite Housed Rod Type Bushing, 126kV Composite Housed Cable Entry Type Bushing, 126kv bushing