Product Overview
The complete set of disconnect switch is composed of a GW4-252 type disconnect switch body, CS14G or CS17G type manual operating mechanism, transmission accessories, etc. It can also be equipped with a motorized operating mechanism such as the CJ6 type.
The disconnect switch is a double-column, horizontally-rotating type. Each single pole consists of a base, support insulators, terminal blocks, contacts, and other components. The two support insulators are installed parallel to each other on bearings at both ends of the base and are perpendicular to the base. The main conductive parts are installed above the two insulators and rotate approximately 90 degrees along with the insulators.
The bearing housing of the disconnect switch is designed as a fully sealed structure to prevent jamming caused by dust, moisture, or harmful gases entering the housing. Inside the bearing housing, thrust ball bearings and radial ball bearings are installed to bear the gravity and horizontal component forces of the disconnect switch. This ensures that the operating torque does not increase after long-term operation. The shaft assemblies of each pole are connected and driven through connecting rods and adjusting screws. Stainless steel pins and self-lubricating bushings are used, and the lubricant is high-performance molybdenum disulfide lithium-based grease.
The copper braided strips in the terminal block are firmly connected to the conductive rod and the terminal plate, which is used for customer line connection.
The contact fingers in the intermediate contact section are assembled in pairs. Springs ensure that the contact fingers tightly clamp the finger block and the contact, reducing wear between the contact and the fingers and extending the service life.
When the disconnect switch is equipped with an earthing switch, the interlock between the main circuit and the earthing switch is ensured by a sector plate and an arc-shaped plate on the base. When the main circuit is closed, the earthing switch cannot be closed, and when the earthing switch is closed, the main circuit cannot be closed.
Technical Specifications
|
Product Name |
Unit |
Parameters |
||
|
Rated Voltage |
kV |
252 |
||
|
Rated Insulation Level |
Power Frequency Withstand Voltage (1min, rms) |
To Earth |
kV |
460 |
|
Across Isolating Distance |
kV |
460+145 |
||
|
Lightning Impulse Withstand Voltage (peak) |
To Earth |
kV |
1050 |
|
|
Across Isolating Distance |
kV |
1050+200 |
||
|
Rated Frequency |
HZ |
50 |
||
|
Rated Current |
A |
1250,1600,2000,2500 |
||
|
Rated Short-Time Withstand Current |
kA |
31.5,40,50,50 |
||
|
Rated Peak Withstand Current |
kA |
80,100,125,125 |
||
|
Rated Short-Circuit Duration (Main / Earthing Switches) |
S |
3/2 |
||
|
Rated Terminal Mechanical Load |
Longitudinal |
N |
1500 |
|
|
Transverse |
N |
1000 |
||
|
Vertical |
N |
1250 |
||
|
Creepage Distance |
MM |
5040,6300,7812 |
||
|
Mechanical Endurance |
Times |
10000 |
||
|
Motor Operating Mechanism |
Type |
CJ6B |
||
|
Motor Voltage |
V |
AC380,AC220,DC220,DC110 |
||
|
Control Circuit Voltage |
V |
AC380,AC220,DC220,DC110 |
||
|
Opening/Closing Time |
S |
8±1 |
||
|
Manual Operating Mechanism |
Type |
CS9,CS14G,CS17G |
||
|
Solenoid Lock Voltage |
V |
AC220,DC220,DC110 |
||
Type Designation and Meaning
G W 4 - 252 □ (W) / □
G: Disconnect Switch
W: Outdoor
4: Design Serial Number
252: Rated Voltage (kV)
□: Equipped with Earthing Switch
(W): Anti-pollution Type
Last □: Rated Current (kA)
Main Technical Parameters
[Note: Technical parameter table is not included here as it was translated separately in the previous interaction. Please insert it at this point if needed.]
Outline and Installation Dimensions
(Diagram corresponds to: GW-220D(G) Type Outdoor AC Disconnect Switch, Three-Pole Linked Arrangement (Right Earthing))
Labeled Components:
| 1. Contact Finger Conducting Arm; | 2. Contact Conducting Arm; | 3. Insulator; | 4. Base; |
| 5. Vertical Rod; | 6. Coupling (Manual Mechanism); | 7. Coupling (Motorized Mechanism); | 8. Manual Operating Mechanism; |
| 9. Motorized Operating Mechanism; | 10. Three-Pole Linkage Rod for Disconnect Switch; | 11. Earthing Switch Conductive Rod; | 12. Earthing Switch Connecting Tube; |
| 13. Earthing Switch Spring; | 14. Earthing Switch Connecting Joint; | 15. Balance Spring Locating Piece; | 16. Earthing Terminal. |
Dimension Labels: Overall Layout: 4000min (Spacing), 2500 (Height), etc.; Detail Dimensions: M16×35, M16×65, M10×65, 4-Φ18, 2-Φ18, etc.; Mounting Holes: 2×Φ24 (Mounting Holes), etc.
Note: For specifications and quantities of accessories, please refer to the packing list.
Hot Tags: gw4-252 outdoor high voltage ac disconnector, China gw4-252 outdoor high voltage ac disconnector manufacturers, suppliers, factory, GN30 12 Indoor Rotary High Voltage Disconnector, disconnector isolator , GN27 GN2 40 5 Indoor High Voltage Disconnector, GN19 12 Indoor High Voltage Disconnector, GW5 40 5 72 5 126 Outdoor High Voltage AC Disconnector, GW4 72 5 126 Outdoor High Voltage AC Disconnector