GW5-40.5 72.5 126 Outdoor High Voltage AC Disconnector
video
GW5-40.5 72.5 126 Outdoor High Voltage AC Disconnector

GW5-40.5 72.5 126 Outdoor High Voltage AC Disconnector

Our GW5 series outdoor disconnectors feature robust double-column design for reliable no-load switching across 40.5kV, 72.5kV, and 126kV systems.

• Rated current up to 2000A with short-time withstand up to 50kA/4s and peak withstand up to 125kA.

• Mechanical endurance of 10,000 operations; optional earthing switches on one or both sides.

• Terminal load capacity of 1000N longitudinal and 750N transverse/vertical for reliable field installation.

• Available in standard and pollution-resistant types with creepage distance up to 3906mm; adaptable to -30°C to +40°C and altitudes up to 2000m.

• Fast delivery, reliable quality, responsive service, and extensive project experience backed by our company.

Model and Its Designation

 

G W 5 - 40.5, 72.5, 126 ☑ (W) □

G: General Purpose Disconnector

W: For Outdoor Installation

5: Design Serial Number

40.5, 72.5, 126: Rated Voltage (kV)

□: Rated Current (A)

(W): Pollution Resistant Type (Optional)

□: Equipped with an Earthing Switch (Optional)

 

Technical Specifications

 

Designation

Unit

Parameter

Rated Voltage

kV

40.5,72.5,126

Rated Insulation Level

1-minute Power-frequency Withstand Voltage (r.m.s.)

to Earth

kV

95,160,230

across the isolating distance

kV

118,200,230+70

Rated Lightning Impulse Withstand Voltage (peak)

to Earth

kV

185,350,550

across the isolating distance

kV

215,410,550+100

Rated Frequency

Hz

50

Rated Current

A

630,1250,1600,2000

Rated Short-time Withstand Current

kA

20,31.5,40,50

Rated Peak Withstand Current

kA

50,80,100,125

Rated Short-circuit Duration

(Main Switch / Earthing Switch)

S

4/2

Rated Terminal Mechanical Load

Longitudinal

N

1000

Transverse

N

750

Vertical

N

750

Creepage Distance

mm

1013,1256,1813,2284,3150,3906

Mechanical Endurance

 

times

10000

Motor-operated Mechanism

Model

 

CJ6B

Motor Supply Voltage

V

AC380,AC220,DC220,DC110

Control Circuit Voltage

V

AC380,AC220,DC220,DC110

Opening Time, Closing Time

S

 

Manual-operated Mechanism

Model

 

CS17,CS17D,CS170D,CS17-G-G₆

Solenoid Lock Supply Voltage

V

AC220,DC110,DC110

Total Weight

Without Earthing Switch

kg

300,350,400

With One Earthing Switch

kg

510,585,660

With Two Earthing Switches

kg

800,900,1000

 

Normal Service Conditions

 

1. Ambient Air Temperature: -30°C to +40°C.

2. Altitude: Not exceeding 2000 m above sea level. (Products for special requirements can be provided).

3. Wind Speed: Not exceeding 34 m/s.

4. Installation Site: Free from flammable substances, explosion hazards, chemical corrosion, and severe vibration.

5. Pollution Class for Post Insulators: Standard Type: Class 0; Pollution Resistant Type: Class II.

Hot Tags: gw5-40.5 72.5 126 outdoor high voltage ac disconnector, China gw5-40.5 72.5 126 outdoor high voltage ac disconnector manufacturers, suppliers, factory, disconnector isolator , GN19 12 Indoor High Voltage Disconnector, GN27 GN2 40 5 Indoor High Voltage Disconnector, GN30 12 Indoor Rotary High Voltage Disconnector, GW13 40 5 72 5 126 Outdoor Neutral Disconnector, GW4 72 5 126 Outdoor High Voltage AC Disconnector