Product Overview
The ZN63(VS1)-12 series indoor high-voltage vacuum circuit breaker is an indoor high-voltage switching device with a three-phase AC 50Hz, rated voltage of 12kV. It serves as a protection and control unit for power equipment in industrial and mining enterprises. The circuit breaker features an integrated design of a spring operating mechanism and the breaker main body. It can be used both as a fixed-installation unit and as a withdrawable truck unit when assembled with a chassis.
Technical Specifications
|
S.Q. |
Name |
|
Unit |
Parameter |
|||
|
1 |
Rated Voltage |
kV |
12 |
||||
|
2 |
Rated Frequency |
Hz |
50 |
||||
|
3 |
Rated Insulation Level |
Power Frequency Withstand Voltage for 1min (RMS) (Phase-to-Phase, Phase-to-Earth, Across Vacuum Interrupter) |
kV |
42 |
|||
|
Lightning Impulse Withstand Voltage (Peak) (Phase-to-Phase, Phase-to-Earth, Across Vacuum Interrupter) |
75 |
||||||
|
4 |
Rated Current |
A |
630 |
630 |
1250 |
1600 |
|
|
1250 |
1250 |
1600 |
2000 |
||||
|
2000 |
2500 |
||||||
|
2500 |
3150 |
||||||
|
4000 |
|||||||
|
5 |
Rated Short-Circuit Breaking Current |
20 |
25 |
31.5 |
40 |
||
|
6 |
Rated Short-Time Withstand Current (Rated Thermal Withstand Current) |
20 |
25 |
31.5 |
40 |
||
|
7 |
Rated Short-Circuit Making Current |
kA |
50 |
63 |
80 |
100 |
|
|
8 |
Rated Peak Withstand Current (Rated Dynamic Withstand Current) |
50 |
63 |
80 |
100 |
||
|
9 |
Rated Short-Circuit Duration (Rated Thermal Withstand Time) |
S |
4 |
||||
|
10 |
Rated Operating Sequence |
O-0.3s-CO-180s-CO |
|||||
|
O-180s-CO-180s-CO (40kA) |
|||||||
|
11 |
Rated Number of Short-Circuit Breaking Operations |
times |
30/20times (40kA) |
||||
|
12 |
Mechanical Life |
times |
6000 |
||||
|
13 |
Rated Single Capacitor Bank Breaking Current |
A |
630 |
||||
|
14 |
Rated Back-to-Back Capacitor Bank Breaking Current |
A |
400 |
||||
|
15 |
Phase-to-Phase Earth Fault Breaking Current |
A |
27 |
||||
|
16 |
Permissible Cumulative Wear Thickness of Moving and Fixed Contacts |
mm |
3 |
||||
Normal Service Conditions
1. The ambient air temperature shall not exceed +40°C, and the daily average temperature shall not exceed +35°C. The minimum ambient air temperature is -15°C. The influence of solar radiation is negligible.
2. Altitude not exceeding 1000 m.
3. Vibrations or movements from outside the switchgear and controlgear are not significantly related to the normal operation of the equipment.
4. The ambient air is not significantly polluted by dust, smoke, corrosive and/or flammable gases, vapors, or salt mist.
5. Humidity Conditions
- The average value of the relative humidity measured over a 24-hour period does not exceed 95%;
- The average value of the water vapor pressure measured over a 24-hour period does not exceed 2.2 kPa;
- The monthly average value of the relative humidity does not exceed 90%;
- The monthly average value of the water vapor pressure does not exceed 1.8 kPa;
Condensation may occasionally occur under these conditions.
For use exceeding the normal service conditions, the permissible limits and technical measures shall be agreed upon between the user and the manufacturer.
Hot Tags: zn63(vs1)-12 series indoor high voltage vacuum circuit breaker, China zn63(vs1)-12 series indoor high voltage vacuum circuit breaker manufacturers, suppliers, factory, indoor vacuum circuit breaker, JYN2 12 and KYN1 12 Type Withdrawable AC Metal Enclosed Switchgear, VZF R 12 Series Indoor AC High Voltage Vacuum Load Break Switch, ZN12 40 5 Series Indoor High Voltage Vacuum Circuit Breaker, ZN23 40 5 Series Indoor Truck Mounted Vacuum Circuit Breaker, ZN85 40 5 Series Indoor High Voltage Vacuum Circuit Breaker