ZN28-12 Series Indoor High Voltage Vacuum Circuit Breaker
video
ZN28-12 Series Indoor High Voltage Vacuum Circuit Breaker

ZN28-12 Series Indoor High Voltage Vacuum Circuit Breaker

Our ZN28-12 indoor vacuum circuit breakers deliver reliable protection for 12kV systems with flexible integrated or separate mounting options, compatible with CD17, CD10A electromagnetic, and CT17, CT19 spring mechanisms.

• Rated at 12kV with current up to 3150A; short-circuit breaking up to 40kA with making current up to 100kA.

• Mechanical life of 10,000 operations with 20–30 short-circuit breaking operations.

• Main circuit resistance ≤50μΩ (≤35μΩ for 40kA); contact gap of 11±1mm with overtravel of 4±1mm.

• Opening time ≤0.06s at max voltage, ≤0.08s at min voltage; closing time ≤0.1s with three-phase asynchrony ≤2ms.

• Contact closing bounce time ≤2ms; average opening speed of 1.2±0.3m/s for reliable fault clearing.

• Fast delivery, reliable quality, responsive service, and extensive project experience backed by our company.

Product Overview

 

The ZN28-12 series vacuum circuit breaker is an indoor high-voltage switching device with a rated voltage of 12kV and a three-phase AC 50Hz. The product complies with the GB1984-89 standard. It is available in two general structural configurations: integrated installation of the switch main body and the operating mechanism, and separate installation of the switch main body and the operating mechanism. The integrated structure is the ZN28-12 basic type; the separate structure is the ZN28-12 type, suitable for fixed-type switchgear such as GG-1A(Z), XGN2A10(Z), etc.

This product can be equipped with CD17, CD10A type DC electromagnetic operating mechanisms and CT17, CT19 type spring-stored energy operating mechanisms.

 

Technical Specifications

 

S.Q

Item

Unit

20kA

25kA

31.5kA

40kA

1

Rated Voltage

kV

12

2

Rated Current

A

630,1000
1250

1250
1600

1250,1600
2000,2500

1600,2500
3150

3

Rated Short-Circuit Breaking Current

kA

20

25

31.5

40

4

Rated Short-Circuit Making Current (Peak)

kA

50

63

80

100

5

Rated Peak Withstand Current

kA

50

63

80

100

6

Rated Short-Time Withstand Current for 4s

kA

20

25

31.5

40

7

Rated Insulation Level

Power Frequency Withstand Voltage (Before & After Rated Breaking)

kV

Power Frequency Withstand Voltage: 42kV (Phase-to-Phase), 48kV (Across the Breaker)

Impulse Withstand Voltage (Before & After Rated Breaking)

Lightning Impulse Withstand Voltage: 75kV (Phase-to-Phase), 85kV (Across the Breaker)

8

Rated Operating Sequence

 

Operating Sequence: O-0.3s-CO-180s-CO

9

Mechanical Life

times

10000

10

Rated Number of Short-Circuit Breaking Operations

times

30

30

30

20

11

Operating Mechanism Rated Closing Voltage

V

110,220

110,220

   

12

Operating Mechanism Rated Closing Current

A

71

71

71

128

13

Operating Mechanism Rated Opening Voltage

V

AC/DC110,220

14

Operating Mechanism Rated Opening Current

A

3.01.5

15

Contact Gap

mm

11±1

16

Overtravel (Contact Spring Compression Length)

mm

4±1

17

Three-Phase Opening & Closing Asynchrony

ms

≤2

18

Contact Closing Bounce Time

ms

≤2

19

Average Opening Speed (At Initial 6mm Opening)

m/s

1.2±0.3

20

Average Closing Speed

m/s

0.6±0.2

21

Opening Time

At Maximum Operating Voltage

S

≤0.06

22

Rated Operating Sequence

At Minimum Operating Voltage

≤0.08

24

Closing Time

S

≤0.1

25

Main Circuit Resistance per Pole

μΩ

≤50

≤50

≤50

≤35

26

Permissible Cumulative Wear Thickness of Moving and Fixed Contacts

mm

3

27

Oil Buffer Stroke

mm

10

 

Normal Service Conditions

 

1. Ambient air temperature: not exceeding +40°C, lower limit -25°C.

2. Altitude: not exceeding 2000 m.

3. Humidity: Daily average relative humidity not more than 95%, monthly average not more than 90%; Daily average water vapor pressure not more than 2.2 kPa, monthly average not more than 1.8 kPa.

4. The ambient air shall not be significantly polluted by corrosive or flammable gases or water vapor.

5. No frequent severe vibration.

6. The inclination angle between the mounting plane and horizontal shall not exceed 5° during contactor operation.

7. Requirements beyond the above conditions shall be agreed upon between the user and the manufacturer.

 

Model and Its Meaning

 

□: Rated Short-Circuit Breaking Current (kA)

□: Rated Current (A)

12-: Rated Voltage (kV)/A: Separate Type

□: Integrated Type

28-: Design Serial Number

N-: Indoor

Z-: Vacuum Circuit Breaker

Hot Tags: zn28-12 series indoor high voltage vacuum circuit breaker, China zn28-12 series indoor high voltage vacuum circuit breaker manufacturers, suppliers, factory, indoor vacuum circuit breaker, JYN2 12 and KYN1 12 Type Withdrawable AC Metal Enclosed Switchgear, ZN12 40 5 Series Indoor High Voltage Vacuum Circuit Breaker, ZN23 40 5 Series Indoor Truck Mounted Vacuum Circuit Breaker, ZN63A VS1 12 Series Indoor Side Mounted Vacuum Circuit Breaker, ZN85 40 5 Series Indoor High Voltage Vacuum Circuit Breaker