Product Overview
The ZW39-40.5 outdoor high-voltage AC vacuum circuit breaker is suitable for use in power systems with an AC rated frequency of 50Hz and a rated voltage of 35kV. It serves as control and protection equipment for power systems. This circuit breaker is suitable for frequent operation and can be used for control and protection in industrial and mining enterprises, power plants, and substations. It can also be employed as a tie circuit breaker.
The circuit breaker complies with the requirements of GB1984-2003 "High-voltage alternating-current circuit-breakers", GB/T11022 "Common specifications for high-voltage switchgear and controlgear standards", and JB/T3855 "High-voltage alternating-current vacuum circuit-breakers". Utilizing vacuum as the insulation and arc-quenching medium and equipped with a CT10-A improved spring operating mechanism, the breaker features high breaking capacity, low operating energy requirements, and high reliability.
Technical Specifications
|
S.Q. |
Item |
Unit |
Parameter |
||
|
1 |
Rated Voltage |
kV |
40.5 |
||
|
2 |
Power Frequency Withstand Voltage |
Phase-to-Earth |
kV |
95 |
|
|
Across Isolating Distance |
kV |
90 |
|||
|
3 |
Lightning Impulse Withstand Voltage (Peak) |
Phase-to-Earth |
kV |
185 |
|
|
Across Isolating Distance |
kV |
185 |
|||
|
4 |
Rated Current |
A |
2000 |
2500 |
|
|
5 |
Rated Short-Circuit Breaking Current |
kA |
31.5 |
||
|
6 |
Rated Short-Time Withstand Current |
kA |
31.5 |
||
|
7 |
Rated Short-Time Duration |
S |
4 |
||
|
8 |
Rated Short-Circuit Making Current (Peak) |
kA |
80 |
||
|
9 |
Rated Peak Withstand Current |
kA |
80 |
||
|
10 |
Rated Number of Short-Circuit Breaking Operations |
times |
30 |
||
|
11 |
Rated Single Capacitor Bank Breaking Current |
A |
630 |
||
|
12 |
Rated Out-of-Phase Breaking Current |
kA |
8 |
||
|
13 |
Rated Phase-to-Phase Earth Fault Breaking Current |
kA |
27.4 |
||
|
14 |
Rated Operating Sequence |
0-0.3s-CO-180s-CO |
|||
|
15 |
Mechanical Life |
times |
10000 |
||
|
16 |
Stored Energy Motor Rated Voltage |
V |
DC220/AC220/DC110 |
||
|
17 |
Rated Operating Voltage |
Opening Coil |
V |
DC220/DC110 |
|
|
Closing Coil |
V |
DC220/DC110 |
|||
Normal Service Conditions
| 1 | Ambient air temperature | -40°C to +40°C; |
| 2 | Altitude | Not exceeding 3000 m; |
| 3 | Wind speed | Not exceeding 34 m/s; |
| 4 | Daily temperature variation | Not exceeding 25°C; |
| 5 | Solar radiation intensity | Not exceeding 0.1 W/cm²; |
| 6 | Monthly average relative humidity | Not exceeding 90%; |
| 7 | Seismic acceleration | Horizontal not exceeding 0.2g, Vertical not exceeding 0.1g; |
| 8 | Ice coating thickness | Not exceeding 10 mm; |
| 9 | Atmospheric pollution severity | Not exceeding Class IV as per GB/T5582; |
| 10 | Installation site | Outdoor. |
If the user has special service condition requirements, please consult with the manufacturer separately.
Hot Tags: zw39-40.5 series outdoor high voltage vacuum circuit breaker, China zw39-40.5 series outdoor high voltage vacuum circuit breaker manufacturers, suppliers, factory, AB 3S 12 Series 12kV Outdoor Permanent Magnet Vacuum Circuit Breaker, ZW17-40.5 Series Outdoor High Voltage Vacuum Circuit Breaker, ZW30A 40 5 Series Outdoor High Voltage Vacuum Circuit Breaker, ZW32 12 Series Outdoor AC High Voltage Vacuum Circuit Breaker, ZW32 24 Series Outdoor High Voltage Vacuum Circuit Breaker, ZW32Y 12 Series Outdoor AC High Voltage Prepaid Vacuum Circuit Breaker