FKRN12A-12 Series 12kV Indoor Gas-Insulated Load Break Switch
video
FKRN12A-12 Series 12kV Indoor Gas-Insulated Load Break Switch

FKRN12A-12 Series 12kV Indoor Gas-Insulated Load Break Switch

Our FKRN12A-12 indoor load break switches and fuse combinations provide reliable protection for 12kV ring main units and compact substations.

• Rated 12kV, 630A; short-circuit making current up to 50kA.

• Interrupts load, overload, and short-circuit currents (up to 31.5kA with fuse).

• Fuse striker opens switch in <0.06s; mechanical endurance of 4000 operations.

• Integrated earthing switch with 20kA/2s withstand.

• Fast delivery, reliable quality, and extensive project experience.

Product Overview

 

The FKN12A-12D compressed-air load break switch and the FKRN12A-12D series of compressed-air load break switch-fuse combination apparatus are suitable for use in three-phase distribution systems of 12kV and below. They serve for the control and protection of power equipment such as transformers, cables, and overhead lines. They are particularly suitable for terminal substations and compact substations in urban and rural power networks. They are also applicable for the control and protection of ring main units and double-feed supply units.

The FKN12A-12D series compressed-air load break switches can interrupt load current and overload current.

The FKRN12A-12D series compressed-air load break switch-fuse combination apparatus can interrupt load current, overload current, and line short-circuit current.

 

Technical Specifications

 

S.Q.

Item

Unit

FN12-12/630

FNR12-12/100-31.5

1

Rated Voltage

KV

12

2

Rated Frequency

HZ

50

3

Rated Current

 

630

125

4

Lightning Impulse Withstand Voltage

KV

75 to ground and between phases, 85 for isolating distance

5

Power Frequency Withstand Voltage (1 min)

KV

42 to ground and between phases, 48 for isolating distance

6

Rated Short-time Withstand (Thermal) Current

KA

20(4S)

 

7

Rated Peak Withstand (Dynamic) Current

KA

50

 

8

Rated Short-circuit Making Current (Peak)

KA

50

50

9

Rated Short-circuit Breaking Current (Prospective)

KA

 

31.5

10

Rated Transfer Current

KA

 

1.5

11

No-load Transformer Breaking Capacity

KVA

1250

12

Rated Cable Charging Current

A

10

13

Mechanical Endurance

KA

4000

14

Fuse Actuated Switch Opening Time

S

 

<0.06

15

Earthing Switch Short-time Withstand Current

KA

20(2S)

 

16

Earthing Switch Peak Withstand Current

KA

50

 

17

Control Circuit Supply Voltage

KA

AC/DC 110,220

 

Model Designation Breakdown

 

FKN 12 A - 12 D / T 630 - 20

F: Load Break Switch

K: Air Insulation

N: Indoor

12: Design Sequence

A: Derivative Code

-: Separator

12: Rated Voltage (kV)

D: Earthing Switch

/T: Spring-operated Mechanism

630: Rated Current (A)

-: Separator

20: Rated Short-time Withstand Current (kA)

 

FKRN 12 A - 12 D / T 630 - 20

F: Load Break Switch

K: Air Insulation

R: Fuse

N: Indoor

12: Design Sequence

A: Derivative Code

-: Separator

12: Rated Voltage (kV)

D: Earthing Switch

/T: Spring-operated Mechanism

630: Rated Fuse Current (A)

-: Separator

20: Rated Short-circuit Breaking Current (kA)

Hot Tags: fkrn12a-12 series 12kv indoor gas-insulated load break switch, China fkrn12a-12 series 12kv indoor gas-insulated load break switch manufacturers, suppliers, factory, electrical load break switches, FKRN12A 12 Series 12kV Indoor Gas Insulated Load Break Switch, FZW32 12 40 5kV Series Outdoor High Voltage Vacuum Isolating Load Break Switch, load break switch, FLW36 12 24 40 5kV Series Outdoor High Voltage SF6 Load Break Switch, transformer load break switch