LN2-40.5 Series Indoor High Voltage SF6 Circuit Breaker
video
LN2-40.5 Series Indoor High Voltage SF6 Circuit Breaker

LN2-40.5 Series Indoor High Voltage SF6 Circuit Breaker

LN2-40.5 Series Indoor High Voltage SF6 Circuit Breaker.

Reliable protection for 40.5kV industrial, mining, and utility applications.

Rated 40.5kV, up to 1600A, breaking up to 31.5kA. Features 800A capacitor bank breaking current, 6000 mechanical operations, and SF6 gas leakage rate ≤1% per year. Suitable for high-altitude and Class II polluted environments.

Product Overview

 

 

The LN2-40.5 indoor high-voltage SF6 circuit breaker is an indoor installation for three-phase 50 Hz AC systems. It is used for protection and control in industrial and mining enterprises, power plants, and substations.

 

Suitable for frequent operation applications, it can also serve as a tie circuit breaker and for switching capacitor banks.

 

 

405kV-vacuum-interrupter-embedded-pole-vertical-3djpg

 

Vertical cross-section of the embedded pole showing internal vacuum interrupter.

 

 

SF6-circuit-breaker-arc-quenching-process-3djpg

 

Puffer-type arc quenching process with high-pressure SF6 gas flow.

 

 

Technical Specifications

 

No.

Item

Unit

Technical Parameter

1

Rated Voltage

kV

40.5

2

Rated Insulation Level

Lightning Impulse Withstand Voltage (Peak)

kV

185

1-minute Power Frequency Withstand Voltage

kV

95

3

Rated Current

A

1250,1600

4

Rated Breaking Current

kA

25

31.5

5

Rated Short-Circuit Making Current

kA

63

80

6

Rated Peak Withstand Current

kA

63

80

7

Rated Short-Time Withstand Current

kA

25

31.5

8

Rated Duration of Short-Circuit

S

4

9

Rated Operating Sequence

 

O-0.3s-CO-180s-CO

10

Rated Capacitor Bank Breaking Current (single)

A

800

11

Rated Out-of-Phase Breaking Current

kA

6.3

12

Closing Time

ms

≤0.15

13

Opening Time

Minimum

ms

≤0.10

Rated

ms

≤0.10

Maximum

ms

≤0.06

14

Number of Operations at Rated Short-Circuit Breaking Current

times

20

15

Mechanical Endurance

times

6000

16

SF6 Gas Leakage Rate (per year)

%

≤1

17

SF6 Gas Moisture Content

PPm(V)

150

18

SF6 Gas Rated Pressure (at 20°C)

MPa

0.65

19

Lockout Pressure (at 20°C)

MPa

0.59

 

 

 Core Advantages 

 

 

  • Seamless Switchgear Integration: Compatible with GBC-40.5, JYN1-40.5, XGN17-40.5, KYN61-40.5, and KYN10-40.5 switchgear. The mechanism panel allows direct status observation and manual operation.
  • High Breaking Capacity: Rated current up to 1600A. Short-circuit breaking current up to 31.5kA, making current up to 80kA (peak). Capacitor bank breaking current up to 800A for versatile scenarios.
  • Reliable & Low Maintenance: Integrated mechanism and arc-extinguishing system reduces closing energy. Mechanical endurance of 6000 operations with SF6 gas leakage rate ≤1% per year.
  • Harsh Environment Ready: Reinforced insulation design meets requirements for high-altitude (up to 2000m), condensation, and Class II polluted environments. Operates reliably from -25°C to +40°C.

 

 

SF6-circuit-breaker-spring-operating-mechanism-3djpg

 

Precision spring operating mechanism for high reliability and low closing energy.

 

 

Model and Its Meaning

 

 

LN2-40.5/1600-31.5

Sulfur hexafluoride circuit breaker

Indoor type

Design serial number

Rated voltage (kV)

Rated current (A)

Rated short-circuit breaking current (kA)

 

Hot Tags: ln2-40.5 series indoor high voltage sf6 circuit breaker, China ln2-40.5 series indoor high voltage sf6 circuit breaker manufacturers, suppliers, factory, LW35 126 Series Outdoor High Voltage SF6 Circuit Breaker, sulfur hexafluoride sf6 circuit breaker, LW24 40 5 Series High Voltage SF6 Circuit Breaker, LW30 126 Series High Voltage SF6 Circuit Breaker, LW 252 Series Outdoor High Voltage SF6 Circuit Breaker, LW30 72 5 Series High Voltage SF6 Circuit Breaker

Send Inquiry